Rack Server Jakarta

RT Series, Single Phase 5/ 6/ 10 kVA

The Amplon RT Series delivers double-conversion on-line technology, high power density and input power factor, and low current harmonics with its advanced architecture.

Designed in a rack or tower configuration with an LCD display, Amplon RT offers advanced performance for servers, data centers, networking, VoIP, and telecommunications.

The Amplon RT has 1+1 parallel redundancy function to provide higher reliabiliity. Optional external battery pack can be added to fulfill longer backup time for mission critical applications.

Applications :

Rack Server Jakarta


  • True online double-conversion topology provides 24/7 fulltime protection
  • 1+1 parallel redundancy or expansion without requiring additional hardware
  • AC-start and battery-start capabilities
  • Additional charger board can be added to reduce recharging time
  • Optional maintenance bypass box for parallel redundancy with manual bypass switch
  • External charger box enhances battery charging ability
  • Rack or tower configuration
  • Multi-language LCD display with blue backlight
  • Optional external battery pack for longer backup time
  • Output factor 0.9 delivers more real power
  • High input power factor (pf > 0.99) and low haromnic distortion (iTHD < 5%)
  • Common battery installation enables two UPS in parallel to share one battery source for cost savings
  • Input voltage range meets the needs of most applications and avoids frequent transfers to battery mode to help prolong battery life
Model   RT-5K RT-6K RT-10K
Power Rating   5 kVA / 4.5 kW 6 kVA / 5.4 kW 10 kVA / 9 kW
Input Nominal Voltage
Voltage Range
Current Harmonic Distortion
Power Factor
Frequency
Electrical Connection
200 / 208 / 220 / 230 / 240 Vac (single phase)
100 ~ 300 Vac
< 5% (full load)
> 0.99 (full load)
40 ~ 70 Hz
Terminal block
Output Voltage
Voltage Harmony Distortion
Voltage Regulation
Frequency
Overload Capability
Electrical Connection
Crest Factor
200 / 208 / 220 / 230(default) / 240 Vac (single phase)
<  2% (linear load)
± 1% (static), ± 2% (typical)
50 / 60 ±0.05 Hz
106 ~ 110% : 10 minutes, 111 ~ 125% : 5 minutes, 126 ~ 150% : 30 seconds
Terminal block
3 : 1
Battery & Charger Nominal Voltage 192 Vdc 192 Vdc 240 Vdc
  Charge Current Built-in maximum 4A (adjustable)
Additional charger board (optional) maximum 4A (internal installation)
Interface Standard RS232 x 1, SMART slot x 1, MINI slot x1, Parallel port x 1
Conformance Safety & EMC CE, EN62040-1, EN62040-2, CISPR 22 Class A
Other Features Parallel Redundancy
Remote Control
Common Battery Installation
1+1
REPO, Remote On / Off
Yes
Efficiency AC-AC
ECO Mode
92% (full load)
96% (full load)
Environment Operating Temperature
Relative Humidity
0 ~ 40°C
0 ~ 95% (non-condensing)
  Audible Noise
(at one meter)
< 56 dBA < 58 dBA < 58 dBA
Physical - Dimensions
(W x D x H)
UPS
Battery Pack
440 x 671 x 89 mm
440 x 638 x 89 mm
440 x 671 x 89 mm
440 x 638 x 89 mm
440 x 623 x 131 mm
440 x 595 x 131 mm
Physical - Weight UPS
Battery Pack
15 kg
36 kg
15.5 kg
36 kg
21.3 kg
66 kg