DPS Series, Three Phase 60 - 400 kVA

Delta's Ultron DPS is a double-conversion and IGBT-rectifier three phase UPS. With state-of-the-art TLI (Triple Level Inverter) and three phase PFC (Power Factor Correction) topology, the Ultron DPS features industry leading performance of up to 96% AC-AC efficiency, input power > 0.99, Low iTHD < 3%, and output power factor up to 0.9. Aiming to achieve the highest availability possible, Delta has enhanced  the design for battery management, swappable fans, and ease of maintenance.
The excellent power performance and high system availability of the Ultron DPS provide customers with the benefits of a stable power supply, high power efficiency, low capital investment, and low overall operation cost.

Applications :


  • N+X redundancy or hot-standby configuration increases system reliability
  • Wide input voltage range (DPS 60-120 kVA : -45% ~ +20%; DPS 160-400 kVA : -40% ~ +20%) allows the UPS to work in unstable electrical environments
  • Field programmable sequential start-up
  • Intelligent fan speed control and redundant fan design prevent overheating
  • Comprehensive battery management sustains battery lifetime and optimal operation
  • High efficiency even at light load saves operating costs
  • Hight input power factor (> 0.99) and low input harmonic distortion (iTHD < 3%) save upstream investment
  • Parallel expansion without extra hardware allows quick capacity upgrade to meet business growth
  • Swappable fans reduce maintenance time
  • Built-in manual bypass allows 'zero-downtime' to ensure system availability during service maintenance
  • Main I/P, O/P and bypass switches detection provide diagnosis when faults occur
Model     DPS-60K DPS-80K DPS-100K DPS-120K DPS-160K DPS-200K DPS-300K DPS-400K
Power Rating - kVA     60 80 100 120 160 200 300 400
Input Nominal Voltage
Voltage Range
Current Harmonic Distortion
Power Factor
Frequency
  380/220V, 400/230V (3 phase, 4-wire +G)
  208 ~ 477 Vac
  < 3%

  >0.99
  50/60 ±5Hz

242 ~ 477 Vac
Output Voltage
Output Power Factor
Voltage Harmonic Distortion
Voltage Regulation
Frequency
Overload Capacity
  380/220V, 400/230V (3 phase, 4-wire +G)
  0.9
  ≤ 3% (linear load)

  ±1% (static)
  50/60 ±0.05Hz
  ≤ 125% : 10 minutes; ≤ 150% : 1 minute


≤ 1.5% (linear load)
Display     Mimic LCD supports multi-language and LED indicators
Interface Standard   RS232 x 1, SMART slot x 2
  Dry contact output x 6
  Dry contact input x 2
  Battery cabinet temperature x 4
  REPO x 1, Parallel port x 2
RS232 x 1, SMART slot x 2
Dry contact output x 6
Dry contact input x 2
Battery cabinet temperature sensor x4
Battery status detection
REPO x 1, Parallel port x 2
  Management Peripherals   SNMP card, Modbus card, Relay I/O control card, EnviroProbe, SNMP hub
Conformance Safety & EMC   EN 62040-1, CE, IEC 62040-2
Other Features Parallel Redundancy and Expansion
Emergency Power Off
Event Log
  Yes (up to 4 units)

  Yes (local and remote)
  500 records
Yes (up to 8 units)


3000 records
Efficiency AC-AC
ECO Mode
  Up to 96%
  Up to 99%
Environment Operating Temperature
Relative Humidity
  0 ~ 40°C
  0 ~ 95% (non-condensing)
  Audible Noise
(at one meter)
< 64 dBA  < 64 dBA < 67 dBA < 67 dBA < 70 dBA < 70 dBA < 73 dBA < 73 dBA
Physical Dimensions (WxDxH)   520 x 975 x 1695 mm 850x 865 x 1950 mm 1600 x 865 x 1950 mm
  Weight   300 kg 330 kg 360 kg 390 kg 697 kg   1335 kg