HPH Series, Three Phase 20/ 30 / 40 kVA

The Ultron HPH is a true online double-conversion UPS offering the best-in-class combination of maximum available power, unbeatable energy efficiency, and superior power performance for small data centers and other mission critical applications requiring highly reliable power protection.
With fully rated power (kVA=kW), the Ultron HPH provides maximum available power without de-rating the UPS. Thanks to Triple Level Inverter and Delta's innovative Three Phase PFC topology, it features low iTHD < 3%, up to 96% AC-AC efficiency, and 99% efficiency in ECO mode resulting in significant TCO (Total Cost of Ownership) savings. Facilitating increased availability through special watch-dog design, the Ultron HPH is an ideal solution for protecting your mission critical operations.

Applications :


  • Fully rated power (kVA=kW) for maximum available power
  • Leading AC-AC efficiency up to 96% saves energy costs
  • Low harmonic pollution (iTHD < 3%) reduces upstream investment costs
  • Wide input voltage range allows the UPS to operate in unstable electrical environments and extends battery life
  • DSP based technology enables reduction in the number of electronic components to lower failure rate
  • Redundant auxiliary power enhances system reliability
  • Watch-dog design of dual auxiliary power circuit to eliminate single-point failure to ensure reliability
  • Built-in manual bypass ensure continous power to the load even if the UPS is under maintenance
  • A wide choice of configurations, such as N+X redundancy, and hot stand-by
  • Adjustable charging current and battery voltage meet different battery configuration requirements
  • Flexible arrangement of battery quantity from 34 to 50 pcs optimize battery investment
  • Multi-connectivity interface supports remote UPS monitoring and management
  • Advanced management software provides remote shutdown, event log tracking and analysis
Model     HPH - 20K
  HPH - 20K - BN/B
HPH - 30K
HPH - 30K - BN/B
HPH - 40K
HPH - 40K - BN/B
Power Rating     20 KW 30 kW 40 kW
Input Nominal Voltage
Voltage Range
Frequency
Power Factor
Current Harmonic Distortion
  220/380 Vac; 230/400 Vac; 240/415 Vac
  -40% ~ 20% (242 ~ 477 / 140 ~276 Vac)
  50/60Hz +/- 10Hz
  > 0.99 (full load)
  < 3%
Output Voltage
Voltage Regulation
Voltage Harmonic Distortion
Overload Capability

Frequency
  220/380 Vac; 230/400 Vac; 240/415 Vac
  ± 1%
  < 1.5 (linear load)
  ≤ 105% : continous; 106% ~ ≤ 125% : 10 minutes
  126% ~ ≤ 150% : 1 minute; > 150% : 1 second
  50/60Hz +/- 0.05Hz
Battery Type
Battery Voltage
Charge Current
Charge Current (BN/B)
Typical Backup Time
  SMF / VRLA
  ±240 Vdc
  5A
  5A, 9A (option)
  15 min


9A

10 min


9A

9.5 min
  Charge Voltage   Float charge ±272V ±2Vdc, Boost charge ±280V ±2Vdc
Communication Interface     SMART slot x 1, MINI slot x 1, Parallel port x 2, RS232 port x 1,
  REPO port x 1, Charge Detection port x 1, Input Dry Contact x 2,
  Output Dry Contact x 6
Conformance Safety & EMC   CE, IEC62040-1, IEC602040-2
Other Features Emergency Power Off
Maintenance Bypass Switch
  Yes (local and remote)
  Yes
Efficiency Online Mode
ECO Mode
  Up to 96%
  Up to 99%
Environment Operating Temperature
Relative Humidity
  0 ~ 40°C
  5 ~ 95% (non-condensing)
  Audible Noise
Protection Level
  < 55 dBA
  IP21
< 60 dBA  
Physical Dimensions (WxDxH)   380 x 800 x 800 mm
  Weight   66.5 kg 86.2 kg 86.5 kg
Physical (BN/B) Dimensions (WxDxH)   490 x 830 x 1400 mm
  Weight (with batt.)
Weight (without batt.)
  365 kg
  131 kg
385 kg
162 kg